Question Number 1: Are Alliance Building, Fire and Electrical safety reports accepted by the ACCORD?
Answer:
The Accord requires independent inspections carried out under the direction of the Accord Chief Safety Inspector. However, the Accord has developed a policy allowing the Chief Safety Inspector to accept Alliance inspections in most circumstances.
Question Number 2: If the boiler is located outside of the factory building, is a fire resistivity wall required?
Answer:
Any room or space housing boilers or other heat producing equipment shall be separated from other spaces by a minimum one hour construction or by a minimum spatial separation of 3 m (10 ft) where located exterior to the building.
Question Number 3: Must fire exit doors be kept open?
Answer:
No, fire doors are normally closed. Fire doors must be equipped with automatic closer and latches. If fire doors are required to behold open for functional reasons, magnetic hold open devices may be provided. Magnetic hold open devices must release upon fire alarm. Wedges under the door or tying the door open are not permitted under any circumstances.
Question Number 4: Are basket type ladders required to be installed?
Answer:
No. Sufficient protected exit stairways are required in all factory buildings.

See full video to gel the all answer...........
 